Chapter 12
109
Technical data
Output circuit (Y14, Y24)
Type of output
N/O contact, connected to internal 24 V DC,
positively guided, current-limited
Number of N/O contacts Y14/24
2
Output voltage
24 V DC (16 … 30 V DC)
Output current
*3
Max. 75 mA
Load capacity
200 nF
General data
Electrical isolation
Supply circuit-input circuit
No
Supply circuit-output circuit
Yes
Input circuit-output circuit
Yes
Weight (without packaging)
186 g (± 5%)
Operating data
Ambient operating temperature
–25 °C … 55 °C
Storage temperature
–25 °C … 70 °C
Air humidity
10 % to 95 %, non-condensing
Climatic conditions
IEC 61131-2, No corrosive gases
Mechanical strength
Vibration resistance
5-150 Hz/1 g (EN 60068-2-6)
10-500 Hz/3 g RMS (EN 60068-2-64)
Electrical safety IEC 61131-2
Impulse voltage withstand level
(Uimp)
4 kV
Overvoltage category
II
Pollution degree
2 inside, 3 outside
Rated voltage
300 V AC
Enclosure rating housing/terminals
IP 40/IP 20 (IEC 60529)
Electromagnetic compatibility
IEC 61131-2, IEC 61000-6-2, EN 55011 class A
Terminal and connection data
Cross-section of connecting wires
Single-core or finely stranded:
0.2 … 1.5 mm
2
(24 to 15 AWG)
Finely stranded with ferrules:
0.25 … 1.5 mm
2
(23 to 15 AWG)
Insulation stripping length
8 mm
Maximum break-away torque
0.6 N·m
*3 The total output current is limited. Maximum total current for all safety relay output modules on Y14
and Y24 is I < 80 mA.
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......