Chapter 4
53
Connecting devices
4.1.6 User
mode
switches
Electrical connection: Example from Setting and Monitoring Tool with WS0-XTIO
Mode switch (1 of 2)
connected to 24 V
Channel 1: Contact between 24 V and I1
Channel 2: Contact between 24 V and I2
Mode switch (1 of 2)
connected to test output
Channel 1: Contact between X1 and I1
Channel 2: Contact between X1 and I3
Function
Notes
Testing Possible
User mode switches without test pulses allow 2 to 8 operating modes; user mode
switches with test pulses allow 2 to 4 operating modes.
When wiring the tested user mode switches it should be noted that odd-numbered
inputs (I1, I3, I5, I7) have to be used if an odd-numbered test output (X1, X3, X5,
X7) is used, and even-numbered inputs (I2, I4, I6, I8) have to be used if an even-
numbered test output (X2, X4, X6, X8) is used.
Further information is available in the manual of the user mode switch.
4.1.7 Potential-free
contacts
The Setting and Monitoring Tool makes a series of potential-free contacts available for
“free” configuration of contact elements. This allows different NC-/NO-contact
combinations with and without testing to be implemented. In addition elements are
available for the start and stop button, reset button and external device monitoring
(EDM).
Function
Notes
Testing Possible
Series connection
Possible
Discrepancy time
See Setting and Monitoring Tool.
Table 31:
Connection of user mode
switches
Table 32:
Function of user mode
switches
Note
Table 33:
Functions of potential-free
contacts
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......