Chapter 12
110
Technical data
Safety specific characteristics
All these data are based on an ambient temperature of +40 °C.
Safety integrity level
SIL3 (IEC 61508)
SIL claim limit
SILCL3 (IEC 62061)
Category
Category 4 (EN/ISO 13849-1)
Performance Level
PL e (EN/ISO 13849-1)
PFD 1.6
×
10
-7
PFHd at I = 0.75 A, switching
frequency = h
-1
(see also Table 61)
1.2 × 10
–9
B10d value, switching frequency = h
-1
0.75 A (AC 15)/4,150,000 (see also Table 61)
SFF 99.6
%
DC 99
%
T
M
(mission time)
Depending on PFHd value, ambient temperature,
load and switching operations (see Table 61)
No. of mechanical switching
operations
Min. 200,000
Load
type
I[A]
Switching frequency
Switching operations
per annum
B10d
PFHd
AC15
0.1
1/h
8760
10,000,000 5.00 × 10
-10
0.75
1/h
8760
4,150,000
1.20 × 10
-09
3
1/h
8760
400,000
1.20 × 10
-08
5
1/h
8760
70,000
7.20 × 10
-08
DC13
1
1/h
8760
2,000,000
2.50 × 10
-09
3
1/h
8760
450,000
1.10 × 10
-08
AC1
2
1/h
8760
1,000,000
5.00 × 10
-09
4
1/h
8760
600,000
8.40 × 10
-09
In order to reach SILCL3 in accordance with IEC 62061 (see chapter 12), the
following test must be made at least every 365 days:
The MELSEC-WS safety controller must be powered down.
The MELSEC-WS safety controller must be powered up.
All safety functions of the connected safety sensors must be verified.
Table 61:
PFHd values WS0-4R0
ATTENTION
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......