App. - 26 App. - 26
APPENDIXES
(a) Switch 1, Switch 3
The following shows the communication rate setting and transmission
setting of the CH1 side (Switch 1) and CH2 side (Switch 3).
Bit Item
Description
b0
Operation setting
OFF (0): Independent
ON (1): Linked
b1 Data
Bit
OFF (0): 7
ON (1): 8
b2
Parity Bit
OFF (0): None
ON (1): Exist
b3 Even/odd
parity
OFF (0): Odd
ON (1): Even
b4
Stop bit
OFF (0): 1
ON (1): 2
b5
Sum check code
OFF (0): None
ON (1): Exist
b6
Online Change
OFF (0): Disable
ON (1): Enable
b7 Setting
modifications
OFF (0): Disable
ON (1): Enable
b8 to b11
Communication rate
(unit: bps)
50 : F
H
, 300 : 0
H
,
600 : 1
H
, 1200 : 2
H
,
2400 : 3
H
, 4800 : 4
H
,
9600 : 5
H
, 14400 : 6
H
,
19200 : 7
H
, 28800 : 8
H
,
38400 : 9
H
, 57600 : A
H
,
115200: B
H
, 230400: C
H
( 1)
b12 to b15
For the system
All 0
1 230400bps can be used via CH1 only.