App. - 6 App. - 6
APPENDIXES
Address
Decimal (Hex)
Protocol
CH1 CH2
Application Name
Initial
value
MC Non Bi Pd
Registration
Reference
Communication system designation (for RS-232)
152
(98
H
)
312
(138
H
)
For designation
of communication
control
0: Full duplex communication
1: Half-duplex communication
0
Simultaneous transmission priority/non-priority designation
153
(99
H
)
313
(139
H
)
0: Priority
1 to 125: Non-priority (transmission wait time, unit: 100 ms)
Retransmission time transmission method designation
154
(9A
H
)
314
(13A
H
)
For half- duplex
communications
control
designation (RS-
232)
0: Do not resend.
1: Resend.
RW
Simultaneously transmission data valid/invalid designation
155
(9B
H
)
315
(13B
H
)
For designation
of communication
control
• Receive data valid/invalid (b0)
0: Valid 1: Invalid
• Transmission data valid/invalid (b8)
0: Valid 1: Invalid
0
— RW
—
Allowed
Chapter 11
Section 7.2
User's Manual
(Application)
No-reception monitoring time (timer 0) designation
156
(9C
H
)
316
(13C
H
)
0
H
: Wait infinitely
28
H
to FA0
H
: Monitoring time (unit: byte)
0
H
RW —
Response monitoring time (timer 1) designation
157
(9D
H
)
317
(13D
H
)
0
H
: Wait infinitely
1
H
to BB8
H
: Monitoring time (unit: 100 ms)
32
H
(5 s)
— RW
Transmission monitoring time (timer 2) designation
158
(9E
H
)
318
(13E
H
)
For designation
of data
communication
time monitoring
0
H
: Wait infinitely
1
H
to BB8
H
: Monitoring time (unit: 100 ms)
708
H
(3
min.)
RW
RW
RW
—
Allowed
Section 7.2
User's Manual
(Application)
159
(9F
H
)
319
(13F
H
)
Use prohibited
System area
—
160
(A0
H
)
320
(140
H
)
Buffer memory head address designation
(400
H
to 1AFF
H
,
2600
H
to 3FFF
H
)
CH1:
400
H
CH2:
800
H
161
(A1
H
)
321
(141
H
)
For designation
of on-demand
function
Data length designation
(0000
H
to 3400
H
)
0
RW
—
Section 7.2
MELSEC-Q/L
MELSEC
Communication
Protocol
Reference
Manual
162
(A2
H
)
322
(142
H
)
Transmission buffer memory head address designation
(400
H
to 1AFF
H
,
2600
H
to 3FFF
H
)
CH1:
400
H
CH2:
800
H
163
(A3
H
)
323
(143
H
)
For designation
of transmission
area
Transmission buffer memory length designation
(0001
H
to 1A00
H
)
200
H
RW
Received data count designation
164
(A4
H
)
324
(144
H
)
0001
H
to 33FE
H
: Received data count
1FF
H
Receive complete code designation
165
(A5
H
)
325
(145
H
)
For data
reception
FFFF
H
: No designation for receive complete code
0
H
to FF
H
: Receive complete code
0D0A
H
:
(CR+
LF)
—
166
(A6
H
)
326
(146
H
)
Receive buffer memory head address designation
(400
H
to 1AFF
H
,
2600
H
to 3FFF
H
)
CH1:
600
H
CH2:
A00
H
167
(A7
H
)
327
(147
H
)
For designation
of reception area
Receive buffer memory length designation
(0001
H
to 1A00
H
)
200
H
RW
Allowed
Receive data clear request
168
(A8
H
)
328
(148
H
)
For data
reception
0: No request
1: Requested
0
— RW
— Not
allowed
Chapter 10
Chapter 11
Section 7.2
Section 10.1.5
First frame No. designation 1st
169
(A9
H
)
329
(149
H
)
0: No designation
Other than 0: Designated
First frame No. designation 2nd
170
(AA
H
)
330
(14A
H
)
0: No designation
Other than 0: Designated
Last frame No. designation 1st
171
(AB
H
)
331
(14B
H
)
0: No designation
Other than 0: Designated
Last frame No. designation 2nd
172
(AC
H
)
332
(14C
H
)
For designation
of on-demand
user frame
0: No designation
Other than 0: Designated
RW —
Section 7.2
User's Manual
(Application)
User frame use enable/disable designation
0: Do not use
1: Use
173
(AD
H
)
333
(14D
H
)
2: Data communication possible (C24 set)
First frame No. designation 1st (1st to 4th)
174 to
177
(AE
H
to
B1
H
)
334 to
337
(14E
H
to
151
H
)
For designation
of receive user
frame
0
H
: No designation
1
H
or more: Head frame No.
0
— RW
—
—
Allowed
Section 7.2
User's Manual
(Application)
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......