15 - 40 15 - 40
15 TROUBLESHOOTING
15.3.5 Read request signal does not turn ON even though the external device transmitted a
message and the "RD" LED was blinking
Symptom Cause
Corrective
action
MC
B
idi
rec
tio
na
l
Non-
proc
edur
al
P
redef
ined
• Communication protocol
is set incorrect.
• Check if the communication protocol is set correctly.
• Check if the mode was switched without using the buffer
memory mode switching area.
Note
• The communication protocol setting contents and the
communication protocol in the current operation can be
checked at communication protocol status (address:
250
H
/260
H
).
• When "Check CD
terminal" was set, the CD
terminal was turned off.
• Since messages are skipped when the CD terminal is
turned OFF when "Check CD terminal" is set, change the
wiring so that the CD terminal remains on all the time.
• When DC control is
selected, the necessary
DC codes are not
transmitted.
• Check if a message is transmitted without transmitting
"DC1 (11
H
)" after the external device transmits "DC3
(13
H
)" during DC1/DC3 external control.
• Check if the next message is transmitted without adding
"DC2 (12
H
)" after the external device transmits "DC4
(14
H
)" during DC2/DC4 external control.
• Use the communication monitoring function to check the
message from the external device.
• The end code was not
received, or fixed length
data was not received.
• Check if the end code set at the C24 and the end code
transmitted from the external device are the same.
• Check if the external device transmitted the fixed length
designated at the C24.
• Check if the trailer frame was transmitted during
communications by user frame.
• Use the communication monitoring function to check the
message from the external device.
Note
• When the send data from the external device is correct,
take the corrective action described in Sections 15.3.11
and 15.3.12.
• The C24 setting and
message format do not
match.
• The data count basics, message format, etc. depend on
the following settings.
• ASCII-BIN conversion enable/disable
• Transparent code setting
• User frame setting
For details of the operation according to the set contents
and setting of each item, refer to the relevant section.
• An external device
transmitted a
message and "RD"
blinked, but the read
request signal
(X3/XA) was not
turned ON.
• The C24 data
communications
monitoring time is set to
"Infinite wait", or the
monitoring time is too
long.
• Set, or shorten, the monitoring time and retransmit the
message from the external device and determine the
trouble from the contents of the time-out error.
Note
• Error detection by the watchdog timer (timer 0 to timer 2)
is possible in the following cases.
• When part of a message is skipped.
• When transmission from an external device is
interrupted.
For details of the monitoring time, refer to the User's
Manual (Application).
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......