6 - 9 6 - 9
6 SETTING AND WIRING
6.3 External Wiring with RS-422/485 Interface
This section explains the specifications of RS-422/485 and how to connect them with
external devices.
6.3.1 RS-422/485 terminal block specifications
The following shows the specifications of the RS-422 connector and RS-422/485
terminal block that connect to an external device.
Mnemonic
Signal name
Signal direction
C24
External device
SDA
SDB
RDA
RDB
SG
FG
FG
Send data (+)
Send data (–)
Receive data (+)
Receive data (–)
Signal ground
Frame ground
Frame ground
SG
SDA
SDB
RDA
RDB
LJ71C24
(FG)
(FG)
(1) The following describes the control signals.
1) SDA, SDB signals
These are signals to send data from the C24 to the external device.
2) RDA, RDB signals
These are signals for the C24 to receive data from the external device.
(2) Terminating resistor
Connect the termination resistor referring section 6.3.3.
(3) Suitable crimp-on terminals
Use 1.25-3 for the solderless terminal to be attached on the terminal block.
Use the UL certified crimp-on terminal. For crimping the terminal, use the tools
recommended by the crimp-on terminal manufactures. Crimp-on terminals with
insulation sleeves cannot be used.
(4) Tightening torque
For details on the tightening torque for the RS-422/485 terminal block, refer to
Section 6.1.1.
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......