7 - 14 7 - 14
7 SETTINGS FOR THE C24
7.3.2 Communication rate setting
Set the communication rate for the data communication with external devices.
The following is the setting value list.
Communication rate
(unit: bps)
50 14400
300 19200
600 28800
1200 38400
2400 57600
4800 115200
9600 230400
1
1 Communication rate of 230,400 bps is available for only CH1.
(1) Precautions
• The transmission speed of the interface, whose communication protocol setting
is set to "MELSOFT Connection", is automatically set to "Auto Setting". In this
case, the data is transmitted at the speed set on GX Works2.
Set "Auto Setting" for the other interface to which no external device is
connected.
• When connecting external devices to both of two interfaces
Perform the setting so that the total of the communication speed of two
interfaces do not exceed 230,400 bps.
• When connecting an external device to either of two interfaces
The maximum of 230,400 bps is available when the external device is
connected to CH1.
The maximum of 115,200 bps is available when the external device is
connected to CH2.
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......