9 - 8 9 - 8
9 DATA COMMUNICATION USING THE PREDEFINED PROTOCOL
(2) Static Data
Use this element when a specific code/character string such as command exists
in a packet.
y
When sending: Sends a specified code and character string.
y
When receiving: Verifies the receive data.
Multiple Static Data elements can be placed to desired positions in the data
division.
The items are the same as ones explained in Section 9.3 (1) in this section.
(3) Terminator
This element indicates the end of a packet. Use this element when a
code/character string indicating the end of the packet is included.
The following table lists the items.
Item Description Remark
Element Name
Set a name of the element.
-
Code Type
Set a data type of the setting value.
ASCII String/ASCII Control Code/HEX
-
Set data within 1 to 50 bytes.
Code type
Setting range
ASCII
String
20
H
to 7F
H
ASCII Control Code 00
H
to 1F
H
, and 7F
H
of control code
HEX
00
H
to FF
H
of hexadecimal data
Setting Value
(Setting example)
ASCII String
: "ABC"
ASCII Control Code: STX
HEX
: FFFF
POINT
y
Only one Terminator can be placed in a packet.
y
Only a Check code and Static Data can be placed behind a terminator.
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......