10 - 15 10 - 15
10 DATA COMMUNICATION USING THE NONPROCEDURAL PROTOCOL
(2) Confirmation using GX Works2, display unit, or indicator LED of
C24
The following methods are available for confirmation.
Item Reference
"Module's Detailed Information"
screen
Chapter 15
"Error History" screen
Chapter 15
GX Works2
"Intelligent Function Module
Monitor" screen
GX Works2 Version1 Operating
Manual
(Intelligent Function Module)
Display unit
Buffer memory monitor
MELSEC-L CPU Module User's
Manual (Function Explanation,
Program Fundamentals)
Indicator LED
of C24
ERR LED turns on
Chapter 15
(3) Precautions
The following shows the precautions of reception data in case of errors.
(a) Storing receive data
The receive data for which an error was detected is discarded and only the
normally received data is stored in the C24.
Thus, there may be missing data among the data that has been read to the
CPU module when a reception error occurs.
(b) Reading receive data
When receive data is read to the CPU module by turning the reception
abnormal detection (X4/XB) ON, the data that was normally received prior to
the error detection is read. Read and discard receive data as needed.
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......