15 TROUBLESHOOTING
15.3.1 The "RUN" LED is turned OFF
Symptom Cause
Corrective
action MC
Bidi
rectio
nal
N
on-
procedural
Predefined
• A transmission setting
switch is set to an
unusable position.
• Set the switch by GX Works2 correctly and
after writing to the CPU module reset the
CPU.
• CPU module error.
• Remove the cause of the CPU module error
and reset the CPU.
Note
• During the C24 and external device
loopback test, the minimum parameters
file must be written to the CPU module
beforehand.
• Power module 5 V
current capacity is
insufficient.
• Calculate the 5 V current drain of each
installed module. If the current capacity is
insufficient, check power module selection.
• Extraneous noise
caused the C24 to
abnormal operation.
• Check if the shielded twisted pair cable is 2-
point ground.
• When ground is used with other devices,
ground the C24 independently.
• The C24 "RUN" LED
turned off.
• The module is not
installed properly.
• Check if the module is installed properly.
• Lock the module joint lever properly.
Содержание MELSEC LJ71C24
Страница 1: ......
Страница 2: ......
Страница 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Страница 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Страница 23: ...A 21 A 21 MEMO...
Страница 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Страница 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Страница 391: ...App 62 App 62 APPENDIXES 3 Refresh parameter setting In Refresh Parameter set the following network parameters...
Страница 425: ......
Страница 426: ......
Страница 427: ......