16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
4. Output specifications (Relay output type)
16.3.2 Parts identification and terminal arrangement
Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower
four points.
Item
FX
2N
-8ER
Output points
4 points
Connection unit
Vertical terminal block (M3 screws)
Output unit
Relay
External power supply
250V AC 30V DC or less
Output circuit insulation method
Mechanical insulation
Indication of output operation
Supplying power to the relay coil will light the LED indicator lamp on panel.
Maximum load
Resistance
load
2 A/point
The total resistance load current per common should be as follows:
• 4 output points/common: 8A or less
Inductive load
80 VA
→
For the product life, refer to Subsection 4.4.2.
→
For cautions on external wiring, refer to Subsection 12.2.4.
Open circuit leakage current
−
Minimum load
5V DC, 2 mA (reference values)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit diagram
Load
DC power
supply unit
Fuse
Y
COM1
FX
2N
-8ER
POWER
0
1
2
3
3
2
1
0
IN
OUT
Without cover
With cover
Input indicator
lamps (LED lamps)
Rear line
extension
connector
Output indicator
lamps (LED lamps)
FX
2N
-
24
+
X0
X1
X2
X3
Y0
Y1
Y2
Y3
CO
M1
FX
2N
-8ER
Содержание FX2-16E series
Страница 2: ......
Страница 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Страница 508: ...FX3U Series Programmable Controllers User s Manual Hardware Edition 500 C Character code C 1 ASCII Code Table MEMO ...
Страница 510: ...502 FX3U Series Programmable Controllers User s Manual Hardware Edition D Discontinued models MEMO ...
Страница 519: ......