FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
245
12 Output Wiring Procedures
12.4 External Wiring for Triac (SSR) Output Type
11
Hi
gh
-Speed
Counters
12
O
utput W
iri
ng
13
W
iri
ng for
V
ari
ous
Us
es
14
Te
st R
un,
Mai
nten
ance,
T
roubl
es
hooti
ng
15
IInput/Output
Pow
ered
Exte
nsi
on U
nit
s
16
Input/O
utput
Extens
ion
Bl
ock
s
17
Extension
Power Suppl
y
Un
it
18
Other Extens
ion
Uni
ts an
d
Opti
ons
19
D
isplay M
od
ule
20
Te
rminal
Bl
oc
k
12.4
External Wiring for Triac (SSR) Output Type
This section explains the triac output specifications (main unit) and external wiring.
• For the main unit, refer to Subsection 12.4.1 "Output specification (main unit) triac output type" and
Subsection 12.4.2 "Handling of triac output" and Subsection 12.4.3 "External wiring precautions" and
Subsection 12.4.4 "Example of external wiring".
• For the input/output powered extension units/blocks, refer to Subsection 12.4.2 "Handling of triac output"
and Subsection 12.4.3 "External wiring precautions". For the specifications and wiring examples, refer to
the specifications for each model.
→
For specifications on the input/output powered extension units, refer to Chapter 15.
→
For specifications on the input/output extension blocks, refer to Chapter 16.
12.4.1 Output specification (main unit) triac output type
Item
Triac output specifications
FX
3U
-32MS/ES
FX
3U
-64MS/ES
Number of output points
16 points
32 points
Connecting type
Removable terminal block (M3 screw)
Output type
Triac output (SSR)
External power supply
85 to 242V AC
Max. load
Resistance load
0.3A / point
The total load current of resistance loads per common terminal should be the
following value.
→
For details on the common terminal for each model,
refer to the terminal block layout.
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 0.8 A or less
Inductive load
15 VA/100V AC, 30 VA/200V AC
Open circuit leakage current
1 mA/100V AC, 2 mA/200V AC
Min. load
0.4 VA/100V AC, 1.6 VA/200V AC
Response time
OFF
→
ON
1 ms or less
ON
→
OFF
10 ms or less
Circuit insulation
Photo-thyristor insulation
Display of output operation
LED on panel lights when photo-thyristor is driven.
Output circuit configuration
Load
Fuse
External
power supply
Y
COM
A common number applies to the of [COM ].
Содержание FX2-16E series
Страница 2: ......
Страница 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Страница 508: ...FX3U Series Programmable Controllers User s Manual Hardware Edition 500 C Character code C 1 ASCII Code Table MEMO ...
Страница 510: ...502 FX3U Series Programmable Controllers User s Manual Hardware Edition D Discontinued models MEMO ...
Страница 519: ......