420
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
19 FX3U-7DM (Display Module)
19.19 User (User-Registered Device Setting)
19.19.5 Program example 3 (when 5 or more devices are displayed as user-registered devices)
Use this program example as a reference when setting 5 or more devices as user-registered devices.
1. Operation
In this program example, the 7 devices shown in the table below are set as user-registered devices, with the
current value display format set individually for each device.
1) The display formats specified here apply only to current values which appear at the "user-registered
device" menu. Other current values appear in decimal format.
2) In this program example, system information is assigned from D50 to D90 and from M50 to M56.
2. Program
Continued on next page
User-Registered Device
No.
Devices Set As User-
Registered Devices
Data Length
Display
Format
1
D100 (D101)
32-Bit
Hexadecimal
2
D102
16-Bit
Decimal
3
D103
16-Bit
Decimal
4
D104
16-Bit
Decimal
5
D200
16-Bit
Hexadecimal
6
D210
16-Bit
Decimal
7
D201
16-Bit
Hexadecimal
MOV
K50
D8300
MOV
K50
D8301
M8002
System information (system No.1) is
set at D50 to D90.
System information (system No.2) is
set at M50 to M56.
K-1
D52
K6
Sets "K-1" at D52 to D57 because user-
registered devices 2 to 4 are unused.
SFTLP
M60
M61
RST
M60
M56
M53
[+] button ON
M61
K7
K1
M67
SET
M60
RST
M67
FMOV
RST
M55
At Monitor/Test screens other than
the "user-registered device" screen,
the current values and setting values
are displayed in decimal format.
M58
M67
ZRSTP
SET
M60
SFTRP
M58
M59
M56
M52
[-] button ON
K8
K1
M59
RST
M59
SET
M66
MOV
K8
D50
MOV
K100
D51
M60
SET
M55
Initialization of the user-registered
screen's scroll flag.
Setting of flag that specifies the
default user-registered devices.
User-registered device screen scroll
program (by the [+] and [-] buttons).
Sets the first device which appears at
the user-registered device screen as
a "D101, D100" 32-bit device, with the
current value displayed in hexadecimal
format.
Initial pulse
M54
M54
M8002
Initial pulse
User-
registered
device
monitoring
in progress
User
message
display
command
User-
registered
device
monitoring
in progress
User
message
display
command