310
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
15.7 FX2N-32ES
3. Output specifications (triac output type)
15.7.2 External dimensions
FX
2N
-32ES
15.7.3 Terminal layout
FX
2N
-32ES
Item
FX
2N
-32ES
Number of output points
16 points
Connection type
Removable terminal block (M3 screw)
Output unit
Triac output (SSR)
External power supply
85 to 242V AC
Output circuit insulation
Insulation with photo-thyristor
Indication of output operation
When photo-thyristor is driven, LED on panel is lit.
Max. load
Resistance
load
0.3A/point
The total load current per common terminal should be the following value.
• 4 output points/common terminal: 0.8 A or less
Inductive load
15 VA/100V AC, 30 VA/200V AC
Open circuit leakage current
1 mA/100V AC, 2 mA/200V AC
Min. load
0.4 VA/100V AC, 1.6 VA/200V AC
Response time
OFF
→
ON
1 ms or less
ON
→
OFF
10 ms or less
Output circuit diagram
Load
Fuse
External
power supply
Y
COM
U
A common number applies to the of [COM ].
7
2
4 5 6
1
3
0
7
2
4 5 6
1
3
0
OUT
IN
L
X1
X3
X5
X7
X6
X0
X2
X4
X6
24+
N
COM
X4
X7
COM4
COM2
Y4
Y5
Y6
Y7
COM3
Y0
Y1
Y2
Y3
COM1
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
X3
X2
X1
X0
X5
FX
2N
-32ES
POWER
7
2
4 5 6
1
3
0
7
2
4 5 6
1
3
0
TRIAC UNIT
150 (5.91")
140 (5.52") (mounting hole pitch)
80 (3.15")
(mounting hole pitch)
90 (3.55")
9 (0.36")
Unit : mm (inches)
87 (3.43")
2-
φ
4.5 mounting holes
The terminal block uses
M3 terminal screws.
X0
COM
24+
N
L
X1
X2
X3
X4
X5
X6
X7
X0
X1
X2
X3
X4
X5
X6
X7
Y4
Y2
Y3
COM2
Y1
Y0
COM1
Y5
Y6
Y7
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
COM3
COM4
Содержание FX2-16E series