FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
459
20 FX-16/32E*-*-TB (Terminal Block)
20.9 FX-16EYS-TB
11
Hi
gh
-Speed
Counters
12
O
utput W
iri
ng
13
W
iri
ng for
V
ari
ous
Us
es
14
Te
st R
un,
Mai
nten
ance,
T
roubl
es
hooti
ng
15
IInput/Output
Pow
ered
Exte
nsi
on U
nit
s
16
Input/O
utput
Extens
ion
Bl
ock
s
17
Extension
Power Suppl
y
Un
it
18
Other Extens
ion
Uni
ts an
d
Opti
ons
19
D
isplay M
od
ule
20
Te
rminal
Bl
oc
k
20.9
FX-16EYS-TB
The FX-16EYS-TB is available by connecting it to a FX
2N
series output extension block (transistor).
The applications shown below are not supported.
20.9.1 Specifications
*1.
In systems where frequent large-load ON/OFF switching occurs due to rush currents, the root mean square
current should be 0.2 A or less.
*2.
This response time does not include the response delay of the PLC.
Output Connector
Connectable models FX
2N
-16EYT-C (sink output)
Unsupported Applications
Pulse
outputs
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width
modulation (PWM) instruction, DOG search zero return (DSZR) instruction, interruption positioning
(DVIT) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS)
instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to
increment (DRVI) instruction, drive to absolute (DRVA) instruction
Time division
inputs
Input matrix (MTR) instruction, hexadecimal input (HKY) instruction, digital switch (DSW) instruction,
arrow switch (ARWS) instruction
Time division
outputs
Seven segment with latch (SEGL) instruction, print (ASCII Code) (PR) instruction
Item
TRIAC output
Input/output
circuitry
Load voltage
85 to 242V AC
Max.
load
Resistance
load
0.3 A / point
*1
The total load current of resistance loads per common terminal should be the
following value:
• 4 output points/common terminal: 0.8A or less
Inductive
load
15 VA / 100V AC
36 VA / 200V AC
Min. load
0.4 VA / 100V AC
1.6 VA / 200V AC
Open-circuit
leakage current
1 mA / 100V AC
2 mA / 200V AC
Response time
*2
2 ms or less
Circuit isolation
Photocoupler isolation
Operation indicator
LED is lit when photo-thyristor power is supplied
Power
consumption
2.7 W (112 mA 24V DC)
0 to 7
COMn
Photo-
thyristor
External wiring
CN1
connector
side
3.3k
Ω
LED
2.2
Ω
0.015
µ
F
7mA
Fuse
U
24+
0.4A
0.7
sec
4A
10
sec
0.02
sec
0.02 + 0.7 + 10
4
2
0.02 + 0.4
2
0.7
= 0.2A
<Example>
Содержание FX2-16E series
Страница 2: ......
Страница 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Страница 508: ...FX3U Series Programmable Controllers User s Manual Hardware Edition 500 C Character code C 1 ASCII Code Table MEMO ...
Страница 510: ...502 FX3U Series Programmable Controllers User s Manual Hardware Edition D Discontinued models MEMO ...
Страница 519: ......