6
-
102
6.17.1Interrupt caused by an error
The CPU module can execute an interrupt program for the interrupt pointer of the error occurred.
(1) Interrupt by an error that can be set to "Continue" or "Stop" in the PLC RAS tab
For an error that is set to "Continue" in the PLC RAS tab of the PLC parameter dialog box, an interrupt can be
executed only for the error.
For an error that is set to "Stop", an interrupt program for all of stop errors (I32) is executed.
(2) Errors corresponding to interrupt pointers
Note20
Figure 6.72 shows the errors corresponding to respective interrupt pointers.
*1: If any of the following serious errors occurs, the interrupt program of I32 is not executed.
• MAIN CPU DOWN
• END NOT EXECUTE
• RAM ERROR
• OPE CIRCUIT ERR.
*2: In the case of a multiple CPU system that includes any High Performance model QCPU or Process CPU, this is applicable
to CPU No.1 only.
Note20
Figure 6.72 List of the error-interrupt pointers
Note6.19
Since no interrupt pointers for errors are provided for the Basic model QCPU, even if an error due to a fault of the CPU
module itself occurs, no interrupt can be executed.
Basic
Note6.20
For the High Performance model QCPU and Process CPU, interrupt pointers I40 and I41 cannot be used.
Also, I33 is applicable to the module whose serial number (first five digits) is "07032" or later.
High
performance
Process
All of stop errors
*1
N/A
Error message
Interrupt pointer
CAN' SWIT
STAND
UNI VERIF ER
FUS BREA OFF
SP.UNI ERRO
OPERATI ERRO
SFC OPE.ERR
SFC
EX.POWER
EXE.ERRO
ICM.OPE.ERR
FIL
OPE.ERR
MULTI CPU ERROR
PRG.TI
OVE
CHK instruction
Annunciator detection
I32
I33
I34
I35
I36
I37
I38
I39
I40
I41
SINGLE PS.DOWN
*2
Errors for which the operation mode after the error is set
to "Continue", or errors that are set to "Continue" from
selection of "Stop/Continue"