(5) Changing a program file in the RUN status
Note3
(a) Methods
Use the following instructions.
• PLOADP instruction (program transfer from memory card to program memory)
• PUNLOADP instruction (program deletion from program memory)
• PSWAPP instruction (program deletion from program memory and program transfer from memory card to
program memory)
For details of each instruction, refer to the following.
MELSEC-Q/L Programming Manual (Common Instruction)
(b) Program setting when a program file is changed
Even if a program file has been changed in the RUN status, the settings configured in the Program tab of the
PLC parameter dialog box are not changed.
When setting the CPU module to STOP, correct the settings in the Program tab of the PLC parameter dialog
box to the settings configured in the RUN status (addition/change/deletion of program name).
Otherwise, an error will occur when the CPU module is set from STOP to RUN.
(6) Boot operation precautions
(a) Storage location of parameters
Store the parameters set in the Boot file tab of the PLC parameter dialog box to the standard ROM or memory
card.
If the parameters are stored in the program memory, the CPU module ignores the parameter settings even if
the parameter-valid drive is set to the program memory with the DIP switches. (
Note3
Note5.3
The Redundant CPU does not support the program file change in the RUN status.