6
-
132
(2) Restrictions that apply to the high speed interrupt only
Table6.37 Restrictions that apply to all the high speed interrupt setting (continued)
Item
Restriction
When used
File register that is the
same name as a
program name
File register that is the same name as a
program name cannot be used.
The high interrupt cannot be executed at the specified intervals
since interrupts are disabled when switching to the file register
that is the same name as a program name. Because of this,
the following time is required.
• 410 s for the standard RAM
• 400 s+100 s Number of program files for an SRAM card
Local device
Local devices cannot be used.
The high interrupt cannot be executed at the specified intervals
since interrupts are disabled when switching to a local device.
Because of this, the following time is required.
• 390 s+170 s n for the standard RAM
• 390 s+950 s n for an SRAM card
(n: number of program files)
Command of the
intelligent function
module that accesses
the CPU module
CPU access commands cannot be issued
from the intelligent function module that
accesses the CPU module such as the
QJ71C24 or QJ71E71.
Since interrupts are disabled when issuing a CPU access
command, the high speed interrupt cannot be executed at the
specified intervals due to delay of the start.
• Reading or writing of N points: (0.07 N+34) s
• Random reading or writing of N points: (0.07 N+101) s
Monitoring via other
stations
Monitoring via any of CC-Link IE Controller
Network modules, MELSECNET/H modules,
or intelligent function modules such as the
QJ71C24 cannot be executed during
monitoring its own station
.
If a self-monitoring request and a request for monitoring via
any intelligent function module are overlapped, interrupt-
disabled time is increased. The high speed interrupt cannot be
executed at the specified intervals due delay of the start
(102 s).
Interrupt counter
The interrupt counter corresponding to
interrupt pointer I49 cannot be used.
Even if the interrupt counter is set, the setting for I49 is
ignored, and the high speed interrupt I49 is executed normally.
(Interrupt programs of other interrupt pointers are not
executed, and the interrupt counter is executed.)
Table6.38 Restrictions that apply to the high speed interrupt only
Item
Restriction
When used
Device comment
In high speed interrupt programs, any device
comment that has the same name as the
program name is not saved and restored.
The written device comment of the high speed interrupt
program is changed.
Index register
In high speed interrupt sequences, the index
register is not saved and restored.
The index register of the high speed interrupt program is
changed.
Access execution flag
(SM390)
In high speed interrupt programs, the access
execution flag SM390 is not saved and
restored.
The SM390 value of the high speed interrupt program is
changed.
Forced on/off
The high speed X/Y refresh area cannot be
forced to turn on or off.
The forced on/off is not executed in the high speed interrupt,
being ignored.
(No timeout error will occur.)
Monitoring condition
setting
No setting is allowed for the high speed
interrupt program.
The setting is not executed normally.
(No timeout error will occur.)
Execution time
measurement
No setting is allowed for the high speed
interrupt program.
The setting is not executed, being ignored.
(No timeout error will occur.)