CHAPTER4 ASSIGNMENT OF BASE UNIT AND I/O NUMBER
4
4.2 I/O Numb
er Assignment
4.2.3 I
/O numb
er setting exa
m
ple
(b) I/O assignment
Select "32 points" for the number of I/O points of Slot 3 in the I/O assignment setting of PLC parameter in GX
Developer.
(c) I/O number assignment after the I/O assignment using GX Developer
Figure 4.12 I/O assignment setting (When changing points of Slot 3)
Figure 4.13 I/O numbers after I/O assignment (After changing points of the empty slot)
Select 32 points. (When
the type is not selected,
the type of the mounted
module will be set.)
Q38B
Q68B
Input module
Input module
Input module
Empty
Output module
Output module
Output module
Output module
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
32
points
0
1
2
4
5
6
7
3
X00
X20
X40
Y80
YA0
YC0 YE0
60
X1F
X3F
X5F
Y9F YBF YDF YFF
7F
Intelligent
function module
Intelligent
function module
Intelligent
function module
Intelligent
function module
Empty
Output module
Output module
Output module
8
9
10
12
13
14
15
11
100
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
120
140
180 Y190 Y1B0 Y1D0
160
11F
13F
15F
18F Y1AF Y1CF Y1EF
17F
The number of I/O points is
changed from 16 points to
32 points.
Extension
1
Number of I/O
points
Slot number
I/O number