'15 • HM-T-246
(3)
Cleaning instructions
1) Turn OFF the power source to the heat pump water heater.
2) Connect pipes.
-) Remove the front panel (control BOX side) and the rear panels ( pcs).
N ote) Remove the fastener at C in order to remove the same at B.
-) Connect hoses from the washing equipment to A and B.
Utilize the hose attachment kit (P CM00A00) to connect to the heat pump water heater (Gas cooler water pipe inlet and outlet).
N ote) P rovide the hoses, pipe connection for hose and clamps locally.
Hot water outlet pipe joint
Screw
A
B
C
A
B
Hose attachment kit
Pipe connection for hose
is locally procured.