'15 • HM-T-246
Compressor stop factor
Number
【
System anomaly
】
HP1 Anomaly
※
63H1 activation
,
HP
≧
14MPa
55
LP1 Anomaly
※
LP
≦
1.0MPa
57
Td1 Anomaly
※
Td
≧
135
℃
59
Open phase on power source, Reverse phase on power source
61
CPU communication error
62
【
System anomaly
】
FMo1 anomaly
65
FMo2 anomaly
66
INV1 current cut
67
INV1 power transistor overheat
69
INV1 start-up failure
71
INV1 communication error
73
INV1 loss of synchronism
75
Communication error between outdoor unit
77
Active filter anomaly
78
【
Water circuit anomaly
】
Water pump anomaly
Ex. Rotation of water pump
<
500 min
-1
80
Inlet water temperature anomaly
Ex1. Inlet water temperature
>
63
℃
Ex2. In case, there Is a temperature
difference(
⊿
10
℃
) in 10 minutes.
81
Outlet water temperature anomaly
Ex1. Outlet water temperature
≧
98
℃
82
Overflow anomaly
83
Anomaly of cut off the water supply
Ex1. Gas cooler outlet refrigerant temperature
≧
80
℃
84
【
Control
】
Normal stop
(
Operation is stopped without anomaly.)
90
Stop for changing control
Ex1. fan control(2fan
→
1fan)
91
Stop for changing water circuit
Ex. Normal operation
→
Keep warm operation(Vented cylinder only)
92
4.9 Compatibility table for water pump
Model
Parts number
Remark
SSA451A010A
SSA451A010B
ESA30E-25
YES
-
ESA30E-25/A
YES
-
ESA30E-25/B
YES
-
ESA30E-25/C
-
YES
Corresponded to Lot11
N ote) When changing the water pump, refer to above list.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание ESA30E-25
Страница 33: ... 15 HM T 246 Rear view Power transformer AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...