'15 • HM-T-246
If 1 group is OFF in combination system, all of unit can not restart by itself.
ON
ON
OFF
source
Power
breaker
Power OFF only 1 group
This warning
message will show
and unit can not
restart by itself
Power source breaker
is needed in each unit.
if this happen, please reset the all of unit.
Power
source
breaker
4.13 Power off in a system with multiple units
(a) Prior to W23R-2.1
(b) W23R-2.2 or later
①
If 1 group power OFF, other group can continue to be in operation.
②
At that time, E1 will be displayed and red light will flash because
there is no communication with remote control and unit(Power OFF).
Power
source
breaker
ON
ON
OFF
Power OFF only 1 group
Red light will
flash
Operation can
continue
Unit protection stop
Will be displayed.
You can confirm error code by
using R/C (Menu
Error
display)
Caution If unit is Power OFF,
below display will be shown for
15 minutes.
Power
source
breaker
Do you want to save up
the previous setting of
R/C before power ON
YES
NO
(1) In case of 1 remote control & multiple units
If 1 group is OFF in combination system, all of unit can not restart by itself.
ON
ON
OFF
source
Power
breaker
Power OFF only 1 group
This warning
message will show
and unit can not
restart by itself
Power source breaker
is needed in each unit.
if this happen, please reset the all of unit.
Power
source
breaker
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание ESA30E-25
Страница 33: ... 15 HM T 246 Rear view Power transformer AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...