'15 • HM-T-246
2.6
Heating system performance characteristics for the operation to top up with
recirculation loop
(1) Heating performance charcteristics table for the operation to top up
(a) Hot water outlet temperature: 60˚C
Heating capacity
P ower consumption
COP
Feed water temperature
Outdoor air temperature
kW
kW
25
30.0
5.38
5.58
16
30.0
6.02
4.98
7
30.0
7.05
4.26
2
30.0
9.93
3.02
-7
30.0
10.42
2.88
-10
28.5
10.22
2.79
-20
24.0
9.51
2.52
-25
21.0
8.91
2.36
17
25
30.0
6.16
4.87
16
30.0
6.82
4.40
7
30.0
7.91
3.79
2
30.0
10.72
2.80
-7
30.0
11.28
2.66
-10
28.5
11.08
2.57
-20
24.0
10.39
2.31
-25
21.0
9.80
2.14
24
25
30.0
6.86
4.38
16
30.0
7.58
3.96
7
30.0
8.77
3.42
2
30.0
11.26
2.66
-7
30.0
11.97
2.51
-10
28.5
11.08
2.57
-20
24.0
11.05
2.17
-25
21.0
10.49
2.00
30
25
30.0
7.89
3.80
16
30.0
8.72
3.44
7
30.0
10.06
2.98
2
30.0
11.83
2.54
-7
30.0
13.02
2.30
-10
28.5
12.82
2.22
-20
24.0
12.07
1.99
-25
21.0
11.30
1.86
(b) Hot water outlet temperature: 65˚C
Hot water outlet temperature: 65
Heating capacity
Power consumption
COP
Feed water temperature
Outdoor air temperature
kW
kW
5
25
30.0
5.83
5.15
16
30.0
6.08
4.93
7
30.0
7.14
4.20
2
30.0
10.09
2.97
-7
30.0
10.59
2.83
-10
28.5
10.88
2.62
-20
24.0
9.73
2.47
-25
21.0
9.03
2.33
17
25
30.0
6.60
4.55
16
30.0
6.98
4.30
7
30.0
8.04
3.73
2
30.0
11.46
2.62
-7
30.0
11.52
2.60
-10
28.5
11.83
2.41
-20
24.0
10.6
2.26
-25
21.0
9.81
2.14
24
25
30.0
7.21
4.16
16
30.0
7.49
4.01
7
30.0
8.65
3.47
2
30.0
11.81
2.54
-7
30.0
11.88
2.53
-10
28.5
12.41
2.30
-20
24.0
11.27
2.13
-25
21.0
10.46
2.01
30
25
30.0
7.94
3.78
16
30.0
9.01
3.33
7
30.0
10.28
2.92
2
30.0
11.83
2.54
-7
30.0
13.02
2.30
-10
28.5
12.82
2.22
-20
24.0
12.06
1.99
-25
21.0
11.29
1.86
<N otes> () The data of power consumption in this table do not include the power consumption of anti-freezing heater (W) .
In case of outdoor air temperature
≦
° C,
please take account of the power consumption for anti-freezing heater.
() For the data of the table and the curve the performance decrement of defrost operation are considered.
But heating performance may change in climate condition and installation environment.
() In water temperature is ° C or more, heating capacity is further reduced. P lease refer to the heating performance characteristics for
the recirculation system in reference.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание ESA30E-25
Страница 33: ... 15 HM T 246 Rear view Power transformer AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...