'15 • HM-T-246
3) Open the drain valve C to drain water. Close the valve after draining.
4) Disconnect the joints from the hot water supply and return pipe sides. Blow air from the hot water supply
pipe joint till no water is forced out from the water supply pipe any more.
* When using a nitrogen gas container, or other, always set the pressure no higher than 0. MP a.
A
B
C
Valves A and B are not used on the units
produced before November 2013.
For the method of water draining from
units equipped without the valves A and
B, refer to separate data.
Hot water supply pipe joint
Water supply pipe joint