16
- 85
16.5 Hardware Self-Diagnostic Function
16.5.2 Hardware self-diagnostic test and initialization setting of the Q06CCPU-V(-B)
16
TROUBLESHOOTING
(2) Before executing the hardware self-diagnostic test and initialization
setting
(a) Removing modules and distribution cables
Remove all the distribution cables and modules except for the power supply
module and C Controller module from the C Controller system.
Note that distribution cables must be connected for executing Mode 3 (RS-232
diagnostic test).
(b) Mounting on CPU slot
Mount the C Controller module on the CPU slot. Otherwise, the diagnostics and
setting cannot be executed.
(c) Preparation required for each mode
Prepare as follows:
1) When executing Mode 1
Disconnect the cable from CH1, if connected.
2) When executing Mode 2
For the Q06CCPU-V, insert a CompactFlash card into the CompactFlash card
slot. (
For the Q06CCPU-V-B, no preparation is necessary.
3) When executing Mode 3
Connect a cable to CH2 as shown below.
4) When executing Mode 1 + 2 + 3
Perform 1) to 3).
Figure 16.27 Cable connection for executing Mode 3
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Pin No.
Signal code
Cable connection
CD(DCD)
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
CI(RI)
Содержание Q06CCPU-V
Страница 2: ......
Страница 612: ...APPX 48 Appendix 11 Functions Added by Version Upgrade APPENDICES Memo ...
Страница 617: ......