![Mitsubishi Electric Q06CCPU-V Скачать руководство пользователя страница 535](http://html.mh-extra.com/html/mitsubishi-electric/q06ccpu-v/q06ccpu-v_user-manual_1811831535.webp)
16
TROUBLESHOOTING
16.4 Error Code List
16.4.1 Error codes and actions (for errors occurred in function execution)
16
- 64
9
DE
V
ICE DE
S
CRIPT
IO
N
10
MU
LT
IPL
E
CP
U SY
S
T
EM
O
V
ER
VI
E
W
11
MUL
T
IP
L
E
CP
U
S
Y
S
TE
M
CONFIGURA
TION
12
CONCE
PT
OF MU
LT
IPL
E
CP
U SY
S
T
EM
13
COMMUN
ICA
TIO
N
S
BE
TWE
E
N
CP
U
MODUL
ES
14
P
A
RAM
E
TE
RS
A
DDE
D
F
O
R MU
LT
IP
LE
C
P
U
S
YSTE
M
S
15
ST
A
R
TIN
G A
M
U
LT
IPLE
CP
U
SYS
TEM
16
TR
O
U
B
L
E
S
HOOTING
* 1 In a single CPU system, reset the C Controller module.
In a multiple CPU system, reset CPU No. 1.
(To the next page)
Table 16.8 Common error codes returned by bus interface and MELSEC data link functions (continued)
Return value
(HEX)
Error description
Corrective action
-28150
(0x920A)
Device access error during data link stop
RX/RY/RWw/RWr was accessed when the own station was not
transmitting data.
Restart the data link.
Note: Writing/reading data will be performed
even when this error occurs. However,
the data are not guaranteed.
-28151
(0x9209)
APS NO. error
Invalid response data were received.
Check if there is an error in the target CPU,
CC-Link module, or MELSECNET/H module.
If the status is normal, try again.
-28155
(0x9205)
SRAM wrtie error
Battery-backed-up RAM writing failed.
Check if an interrupt routine (interrupt program)
is writing data into the same battery backed-up
RAM area.
Change the C Controller module if the error
persists.
-28158
(0x9202)
WDT error
Watchdog timer (WDT) error occurred.
Reboot the operating system.
*1
Reset the module.
-28410
(0x9106)
Target CPU busy error
Target CPU is busy.
Add a program to wait until the processing is
completed or to retry.
Increase the timeout value in the user program.
-28412
(0x9104)
Target CPU unsupported error
An unsupported request was sent to the target CPU.
Change the target CPU No. in the user
program.
-28413
(0x9103)
Target CPU down error
Check the operating status of the target CPU
and trouble shoot the error.
-28414
(0x9102)
Target CPU abnormal start error
A request was sent to the CPU which was not operating normally.
Check the operating status of the target CPU
and trouble shoot the error.
-28415
(0x9101)
Target CPU critical error
A request was sent to the CPU where a critical error occurred.
Check the operating status of the target CPU
and troubleshoot the error.
-28416
(0x9100)
Target CPU not mounted error
Check if the target CPU is mounted properly.
Change the target CPU No. specified in the
user program.