11
- 15
11.3 Precautions for System Configuration
11
MULTIPLE CPU SYSTEM CONFIGURATION
(2) Combinations of power supply modules and base units
Some restrictions are applied to the combinations of power supply modules and base
units.
(
(3) Precautions for GOT connection
The GOTs that can be used for the C Controller module are the same as those usable
in a single CPU system. (
(4) Precautions for MT Developer (Version 00Y or earlier) connection in a
multiple CPU system
When a multiple CPU system includes a C Controller module as CPU No.1 and a
Motion CPU, a communication test of MT Developer (Version 00Y or earlier) are
cannot be performed. (The Motion CPU communication test error (error code: 12288)
will occur.)
To perform the communication test from MT Developer, use either of the following
methods.
• Use MT Developer of Version 00Z or later.
• When using MT Developer of Version 00Y or earlier, modify the multiple CPU
system configuration so that CPU No.1 is a programmable controller CPU.
(5) Time adjustment and time notification of GOT
In a multiple CPU system configuration, when the time adjustment or notification is
performed in GOT connected to C Controller modules for CPU No. 2 to No. 4, it is
executed to CPU No. 1.
In this case, to match the clock data between C Controller modules for CPU No. 2 to
No. 4 and GOT, use the multiple CPU clock synchronization function.