(5) Precautions
Pay attention to the following since the C Controller module gives priority to STOP.
(a) STOP timing
The C Controller module is stopped when remote STOP is executed from either of
the user program or C Controller setting utility.
(b) Changing the remote STOP status to RUN again
To change the C Controller module status from remote STOP to RUN again,
execute remote RUN.
(
(c) Output (Y) status during STOP
When "Output mode at STOP to RUN" is set to "Previous state" in <<System
settings>> of C Controller setting utility, the output (Y) data at the time when RUN
is changed to STOP are output in remote RUN mode.
(d) User program during STOP
The user program will not stop even if the C Controller module is placed in the
remote STOP status. (Operation continues inside the C Controller module.)
To change the program processing according to the operation status of the C
Controller module, utilize bus interface functions (QBF_ReadStatusEx) in
programming.
Remark
The operation status of the C Controller module can be confirmed by the
following.
• Bus interface function (QBF_ReadStatusEx)
• C Controller setting utility ("CPU operation status" on <<Module
information>>)