6
- 74
6.10 Initializing/Changing Mode of C Controller Module
6.10.1 Initializing/Changing mode of Q12DCCPU-V
6
PREPARATORY PROCEDURES AND SETTING
(4) Settings and file conditions after the operations
The following table indicates the settings and file conditions after executing the
"Default IP setting" mode or performing the module initialization setting procedure.
* 1 The setting returns to the default IP address.
Default IP address for CH1: 192.168.3.3
Default IP address for CH2: No setting
* 2 Previous information is deleted.
* 3 Previous data before execution of the default IP setting mode are retained.
* 4 The startup script file "STARTUP.CMD" in the standard RAM is deleted.
The "STARTUP.CMD" saved in the standard RAM before execution of the default IP setting mode
is renamed to "STARTUP.BAK" and saved to the standard RAM. (If "STARTUP.BAK" already
exists, it is overwritten.)
Table 6.21 File conditions
File type
Settings and file conditions
Default IP setting
Module initialization
setting
IP address setting
*1
*1
Event history file
*2
C Controller module parameters
*3
Default parameters
CC-Link module parameters
*3
Deleted
MELSECNET/H module parameters
*3
Deleted
CC-Link IE controller network module
parameters
*3
Deleted
Intelligent function module parameters
*3
Deleted
Script file
*4
Deleted
User program
*3
Deleted
Files used in the user program
*3
Deleted