1 SERVO PARAMETER DETAILS
1.7 Extension setting 3 servo parameters group ([Pr. PF_ _ ])
93
1
[Pr. PF21_Drive recorder switching time setting (DRT)]
Set the drive recorder switching time.
When communication is shut off during the use of a graph function, the function will be switched to the drive recorder function
after the time set in this servo parameter has passed.
When "-1" is set, the drive recorder function is disabled.
When "0" is set, the drive recorder function will be switched after 600 s (10 min).
When any value of "1" to "9" is set, the drive recorder function will be switched after 10 s.
When any value of "10" to "32767" is set, the drive recorder function will be switched after the time set in this servo parameter
has passed.
[Pr. PF23_Vibration tough drive - Oscillation detection level
(OSCL1)]
Set the oscillation detection level for readjusting the machine resonance suppression filter while the vibration tough drive is
enabled.
When the oscillation level is higher than the setting value of this servo parameter, reset [Pr. PB13 Machine resonance
suppression filter 1] or [Pr. PB15 Machine resonance suppression filter 2].
When "0" is set, the oscillation detection level is 20 %.
[Pr. PF24_Function selection F-9 (*FOP9)]
[Pr. PF24.0_Oscillation detection alarm selection]
Select the alarm output at oscillation detection.
Select whether to generate an alarm or a warning when an oscillation continues at a level set in [Pr. PF23 Vibration tough
drive - Oscillation detection level].
This function is enabled regardless of the setting of [Pr. PA20.1 Vibration tough drive selection].
0: Alarm ([AL. 054 Oscillation detection])
1: Warning ([AL. 0F3.1 Oscillation detection warning])
2: Oscillation detection function disabled (oscillation detection not processed)
Initial value
Setting range
Setting method
Ver.
0 [s]
-1 to 32767
Common
C4
Initial value
Setting range
Setting method
Ver.
20 [%]
0 to 100
Each axis
C4
Initial value
Setting range
Setting method
Ver.
00000000h
Refer to the relevant detail No.
Each axis
Refer to the relevant detail No.
Initial value
Setting range
Ver.
0h
Refer to the text
C4