![Mitsubishi Electric FX3G SERIES Скачать руководство пользователя страница 910](http://html.mh-extra.com/html/mitsubishi-electric/fx3g-series/fx3g-series_programming-manual_238902910.webp)
908
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-1 Basic Instruction Execution Time
Appendix B: Instruction Execution Time
The instruction execution time in FX
3G
, FX
3U
and FX
3UC
PLCs is as shown below:
Measurement condition
• High-speed counters and interrupt instructions (I) are not used together.
• In operands, data registers are used as target devices.
• Indexing (V or Z) is not provided.
Appendix B-1 Basic Instruction Execution Time
• FX
3U
/FX
3UC
PLCs
Instruction
Execution time in ON status (
μ
s)
Execution time in OFF status (
μ
s)
Remarks
16-bit instruction
32-bit instruction
16-bit instruction
32-bit instruction
Contact instructions
LD
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
LDI
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
LDP
7.8
⎯
LDF
7.8
⎯
AND
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
ANI
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
ANP
7.5
⎯
ANF
7.5
⎯
OR
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
ORI
0.065
0.129
μ
s in 2-step instruction
*1
0.193
μ
s in 3-step instruction
*3
ORP
7.4
⎯
ORF
7.4
⎯
Connection instructions
ANB
0.065
ORB
0.065
MPS
0.065
MRD
0.065
MPP
0.065
INV
0.065
MEP
3.4
MEF
3.4
Output instructions
OUT Y,M
0.065
0.129
μ
s in 2-step instruction
*2
0.193
μ
s in 3-step instruction
*3
OUT S
4.8
4.8
OUT T K
0.71
0.71
T192 to T199, T246 to T511
11.6
μ
s in execution in ON status
8.2
μ
s in execution in OFF status