24 Others – FNC181 to FNC189
24.3 FNC186 – DUTY / Timing Pulse Generation
4) When the command input is set to ON, the operation is started. The timing clock output destination device
is set to ON or OFF by the END instruction.
Even if the command input is set to OFF, the operation is not stopped.
In the STOP mode, the operation is suspended. When the power to the PLC is turned OFF, the operation is
stopped.
5) When "n1" and "n2" are set to "0", the device
is set to the following status:
Related devices
Caution
• The DUTY (FNC186) instruction can be used up to 5 times (points).
It is not permitted, however, to use the same timing clock output destination device
for two or more DUTY
(FNC186) instructions.
Errors
An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in
D8067.
• When "n1" and/or "n2" is less than "0" (error code: K6706)
• When any device other than M8330 to M8334 is set to
(error code: K6705)
Program example
In the program shown below, when X000 is set to ON, M8330 is set to ON for 1 scan and OFF for 3 scans.
n1/n2 status
ON/OFF status
n1 = 0, n2
≥
0
Fixed to OFF
n1 > 0, n2 = 0
Fixed to ON
Device
Name
Description
M8330
Timing clock output 1
Timing clock output in the DUTY (FNC186) instruction
M8331
Timing clock output 2
M8332
Timing clock output 3
M8333
Timing clock output 4
M8334
Timing clock output 5
D8330
Counted number of scans for
timing clock output 1
Counted number of scans for timing clock output 1 in the DUTY (FNC186) instruction
D8331
Counted number of scans for
timing clock output 2
Counted number of scans for timing clock output 2 in the DUTY (FNC186) instruction
D8332
Counted number of scans for
timing clock output 3
Counted number of scans for timing clock output 3 in the DUTY (FNC186) instruction
D8333
Counted number of scans for
timing clock output 4
Counted number of scans for timing clock output 4 in the DUTY (FNC186) instruction
D8334
Counted number of scans for
timing clock output 5
Counted number of scans for timing clock output 5 in the DUTY (FNC186) instruction
D
D
D
D
D
D
D
X000
FNC186
DUTY
K3
M8330
END
K1
OFF
OFF ON
ON
X000
M8330
1 scan
3 scans
0
1
2
3
0
1
D8330
current value