38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FNC276
-F
NC2
79
Da
ta
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
Register
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
p
Inform
ati
on
B
Ex
ecuti
on
T
imes
Circuit error [M8066(D8066)]
0000
⎯
No error
6610
Stops
operation
LD, LDI is continuously used 9 times or more.
This error occurs when a combination of instructions is
incorrect in the entire circuit block or when the
relationship between a pair of instructions is incorrect.
Modify the instructions in the program mode so that their
mutual relationship becomes correct.
6611
More ANB/ORB instructions than LD/LDI instructions
6612
Less ANB/ORB instructions than LD/LDI instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
6616
No coil between MPS, MRD and MPP, or incorrect
combination
6617
Instruction below is not connected to bus line:
STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET,
FEND or END
6618
STL, MC or MCR can only be used in main program, but
it is used elsewhere (e.g. in interrupt routine or
subroutine).
6619
Invalid instruction is used in FOR-NEXT loop:
STL, RET, MC, MCR, I (interrupt pointer) or IRET.
6620
FOR-NEXT instruction nesting level exceeded
6621
Numbers of FOR and NEXT instructions do not match.
6622
No NEXT instruction
6623
No MC instruction
6624
No MCR instruction
6625
STL instruction is continuously used 9 times or more.
6626
Invalid instruction is programmed within STL-RET loop:
MC, MCR, I (interrupt pointer), SRET or IRET.
6627
No STL instruction
6628
Invalid instruction is used in main program:
I (interrupt pointer), SRET or IRET
6629
No P or I (interrupt pointer)
6630
No SRET or IRET instruction
STL-RET / MC-MCR instructions programmed in the
subroutine.
6631
SRET programmed in invalid location
6632
FEND programmed in invalid location
Error
code
PLC operation at
error occurrence
Contents of error
Action
Содержание FX3G SERIES