Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
30 External Device Communication (Inverter Communication) – FNC270 to FNC275
30.6 FNC275 – IVMC / Inverter Multi Command
3. Related devices
→
For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1.
Cleared when PLC power supply is turned from OFF to ON.
*2.
Cleared when the PLC mode switches from STOP to RUN.
*3.
Initial value: -1
Cautions
→
For other cautions, refer to the Data Communication Edition manual.
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and
an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
• Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same
time.
• Number of occupied devices
Two devices are occupied respectively by
and
.
Make sure not to use those devices in another control.
• If a device number outside the range due to indexing, etc. is specified in
, the receive data from the inverter
is not stored in
. However, values set in
and
+1 may be written to the inverter.
• If any unspecified value is set in
, unexpected data may be written to and read from the inverter, and values
of
and +1
may
be
updated.
• IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the read status
to
. Accordingly, the status written by the IVMC instruction can be read by a next or later read instruction
(IVCK or IVMC).
Applicable inverters
This instruction is applicable to the following inverters:
- FREQROL-E700(February 2009 and later)
- FREQROL-D700(Applicable in all)
→
For details, refer to the respective inverter manual
Applicable programming tool
This instruction is applicable to the following programming tools:
• FX
3U
/FX
3UC
Series PLC
• FX
3G
Series PLC
Number
Description
Number
Description
ch1
ch2
ch1
ch2
M8029
Instruction execution complete
D8063 D8438 Error code of serial communication error
*1
M8063 M8438 Serial communication error
*1
D8150 D8155 Response wait time in inverter communication
*1
M8151 M8156 Inverter communicating
D8151 D8156 Step number in inverter communication
*3
M8152 M8157 Inverter communication error
*2
D8152 D8157 Error code of inverter communication error
*2
M8153 M8158 Inverter communication error latch
*2
D8153 D8158 Latch of inverter communication error occurrence step
*2*3
M8154 M8159 Inverter instruction error
*2
D8154 D8159 IVBWR instruction error parameter number
*2*3
Model name (Media model name)
Compatible Versions
Remarks
GX Works2 (SW
DNC-GXW2-J)
Ver. 1.45X or later
GX Works2 (SW
DNC-GXW2-E)
Ver. 1.48A or later
FX-30P
Ver. 1.20 or later
Model name (Media model name)
Compatible Versions
Remarks
GX Works2 (SW
DNC-GXW2-J)
Ver. 1.56J or later
GX Works2 (SW
DNC-GXW2-E)
Ver. 1.62Q or later
S
3
D
D
D
S
3
S
3
S
2
D
D
D