341
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
13 High-Speed Processing – FNC 50 to FNC 59
13.1 FNC 50 – REF / Refresh
11
FN
C30
-FN
C3
9
R
ota
tion and
Shi
ft
12
FN
C40-FN
C49
D
ata O
perati
on
13
FNC
50-FNC
59
High-Speed
Proc
essing
14
FM
C60-FN
C69
H
andy
In
struction
15
FN
C70-FN
C79
E
xternal
F
X
I/O
De
vice
16
FNC
80-FNC
89
External
FX
Dev
ice
17
FNC1
00-
FNC10
9
Dat
a
Transfer 2
18
FNC1
10-
FNC139
Fl
oa
ting Poi
nt
19
FNC14
0-F
N
C
149
Da
ta
Operation 2
20
FNC1
50-
FNC159
Pos
itioning
Control
Cautions
1. Setting the number of refreshed points "n"
Set a multiple of 8 such as "K8 (H8), K16 (H10)
…
K256 (H100)". Any other numeric value causes an error.
2. Setting the head device number (D)
Make sure that the least significant digit number is "0" such as "X000, X010, X020
…
"or " Y000, Y010, Y020
…
"
Program examples
1. When refreshing inputs
Only X010 to X017 (8 points in total) are refreshed.
2. When refreshing outputs
Y000 to Y007, Y010 to Y017 and Y020 to Y027 (24 points in total) are refreshed.
ON
ON
20ms
5ms
10ms
10ms
Does not turn ON.
ON
10ms
Input signal (X)
Filter time
Input refresh
REF instr END processing
END instruction (input) processing
Input terminal
REF instruction (executed)
Only END processing
Improved response
delay time
X000
FNC 50
REF
X010
K 8
D
n
X001
FNC 50
REF
Y000
K 24
D
n