37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
Stepladder and Annunciator
[D]8040
*1
ON state number 1
The smallest number out of active state ranging from S0 to
S899 and S1000 to S4095
*2
is stored in D8040 and the
second-smallest state number is stored in D8041.
Active state numbers are then sequentially stored in
registers up to D8047 (Max. 8 points).
3
3
3
M8047
3
3
3
3
3
[D]8041
*1
ON state number 2
3
3
3
3
3
3
3
3
[D]8042
*1
ON state number 3
3
3
3
3
3
3
3
3
[D]8043
*1
ON state number 4
3
3
3
3
3
3
3
3
[D]8044
*1
ON state number 5
3
3
3
3
3
3
3
3
[D]8045
*1
ON state number 6
3
3
3
3
3
3
3
3
[D]8046
*1
ON state number 7
3
3
3
3
3
3
3
3
[D]8047
*1
ON state number 8
3
3
3
3
3
3
3
3
[D]8048
Not used
–
–
–
–
–
–
–
–
–
[D]8049
*1
On state minimum
number
When M8049 is ON, the smallest number out of active
annunciator relay ranging from S900 to S999 is stored in
D8049.
3
3
3
M8049
–
–
3
–
3
[D]8050 to [D]8059
Not used
–
–
–
–
–
–
–
–
–
*1.
Executed at END instruction.
*2.
S1000 to S4095 are available only in FX
3G
/FX
3U
/FX
3UC
PLCs.
Error Detection (Refer to Chapter 38 for details.)
[D]8060
If the unit or block corresponding to a programmed
I/O number is not actually loaded, M8060 is set to ON and
the first device number of the erroneous block is written to
D8060.
3
3
3
M8060
–
–
3
–
3
[D]8061
Error code for PLC hardware error
3
3
3
M8061
3
3
3
3
3
[D]8062
Error code for PLC/PP communication error
3
3
3
M8062
–
–
3
–
3
Error code for serial communication error 0 [ch0]
*4
3
–
–
M8062
–
–
–
–
–
[D]8063
*5
Error code for serial communication error 1 [ch1]
3
3
3
M8063
3
3
3
3
3
[D]8064
Error code for parameter error
3
3
3
M8064
3
3
3
3
3
[D]8065
Error code for syntax error
3
3
3
M8065
3
3
3
3
3
[D]8066
Error code for ladder error
3
3
3
M8066
3
3
3
3
3
[D]8067
*6
Error code for operation error
3
3
3
M8067
3
3
3
3
3
D 8068
Operation error step number latched
3
3
*7
3
*7
M8068
3
3
3
3
3
[D]8069
*6
Error step number of M8065 to M8067
3
3
*8
3
*8
M8065 to
M8067
3
3
3
3
3
*3.
10 to 337 in FX
3U
, FX
3UC
, FX
2N
and FX
2NC
PLCs, and 10 to 177 in FX
3G
PLCs
*4.
Cleared when PLC power supply is turned from OFF to ON.
*5.
The operation varies according to PLC:
-
Cleared in an FX
1S
, FX
1N
, FX
2N
, FX
1NC
, or FX
2NC
when PLC switches from STOP to RUN.
-
Cleared in an FX
3G
, FX
3U
, or FX
3UC
PLC when PLC power supply from OFF to ON.
*6.
Cleared when PLC switches from STOP to RUN.
*7.
In case of 32K steps or more, step number is stored in [D8313, D8312].
*8.
In case of 32K steps or more, step number is stored in [D8315, D8314].
Number and name
Content of register
Applicable model
FX
3G
FX
3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX
2NC
1 0 2 0
1: Input X 0: Output Y
Device number
Example: If X020 is unconnected.
BCD converted value
*3