4 Devices in Detail
4.9 Data Register and File Register [D]
2) When file registers of different device numbers are specified for the source and destination
Write
• When X001 is set to ON, the contents of the data
register area [B] are transferred to the data register
area [B] and file register area [A] as shown in the
figure on the left.
If data cannot be written to the file register area [A]
because the protect switch of the memory cassette is
ON, data is written to only the data register area [B].
4.9.5
Cautions on using file registers
1. Cautions on using a memory cassette
When changing the contents of file registers stored in the memory cassette, confirm the following conditions:
• Set to OFF the protect switch in the memory cassette.
• In FX
3U
/FX
3UC
PLCs
- It takes 66 to 132 ms to write data in one continuous block (500 points) to the memory cassette (flash memory).
Execution of the program is paused during this period. Because the watchdog timer is not refreshed during this
period, it is necessary to take proper countermeasures such as inserting the WDT instruction into the sequence
program.
- Do not turn OFF the power while the contents of file registers are changed.
If the power is turned OFF during the change, the data stored in file registers may be filled with unexpected
values, or a parameter error may occur.
• In FX
3G
PLCs
It takes 80 ms to write data in one continuous block (500 points) to the memory cassette (EEPROM).
Note that execution of the program is paused during this period, but the watchdog timer is automatically refreshed.
2. Allowable number of writes to the memory
• Data can be written to the memory cassette up to 10,000 times, and to the memory (EEPROM) built in FX
3G
PLCs
up to 20,000 times.
When a continuous operation type instruction is used for data writing in a program, data is written to the memory in
every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction (BMOVP).
3. Cautions on handling file registers in the same-number register update mode in BMOV (FNC 15)
instruction
• When updating the contents of the same number file register, make sure that the file register number at
and
are equal to each other.
• Make sure that the number of transfer points specified by "n" does not exceed the file register area.
• If the number of transfer points specified by "n" exceeds the file register area, an operation error (M8067) occurs
and the instruction is not executed.
• In the case of indexing
When
and
are indexed, the instruction is executed if the actual device number is within the file
register area and the number of transfer points is within the file register area also.
Write
Data register
[B]
Inside system
RAM
Inside built-in
memory or
memory cassette
Program
memory
Program/
comment
File register
[A]
D1000
Data
memory
Data register
Data register
D7999
D 0
D1400
D1499
D1499
D1100
Write
500 points
×
14 blocks
maximum
(7000 points
maximum)
D1400
D1199
X001
FNC 15
BMOVP
D1100
D1400
K100
S
D
n
OFF
M8024
S
D
S
D