3.3 Parameter Checking and Setting
OPERATION/CONTROL
54
3.3 Parameter Checking and Setting
The inverter is designed to perform simple variable-speed operation with the factory settings of the
parameters. Set the necessary parameters according to the load and operation specifications. Use the
operation panel (FR-DU04) to set, charge and confirm the parameter values. For full information on the
parameters, refer to “CHAPTER 4 PARAMETERS”(Page 62).
3.3.1 Parameter checking
Pr. 160 "user group read selection" is factory-set to display only the simple mode parameters among the
parameters. Set the following parameters as required.
(1) Pr. 160 "user group read selection"
Parameter
Number
Factory Setting
Setting Range
160
9999
0, 1, 10, 11, 9999
•
Setting details
For the setting method and in-depth explanation, refer to page 139.
Pr. 160 Setting
Description
0
All parameters are made accessible for reading and writing.
1
Only the parameters registered in user group 1 are made accessible for reading and writing.
10
Only the parameters registered in user group 2 are made accessible for reading and writing.
11
Only the parameters registered in user groups 1 and 2 are made accessible for reading and
writing.
9999
Only the simple mode parameters are made accessible for reading and writing. (Factory setting)
(2) Simple mode parameter list
The following parameters are basic parameters made accessible for reading and writing by setting "9999" in
Pr. 160. For details of their functions, refer to Chapter 4 "PARAMETERS" (page 62).
Parameter
Number
Name
Application
Refer to
0
Torque boost
Used to compensate for a voltage drop in the low frequency range to
improve motor torque reduction in the low speed range.
68
1
Maximum frequency
2
Minimum frequency
Used to set the upper and lower limits of the output frequency.
69
3
Base frequency
Used to match the inverter outputs (voltage, frequency) to the motor
rating.
70
4
Three-speed setting (high speed)
5
Three-speed setting (middle speed)
6
Three-speed setting (low speed)
Set these parameters when using the terminals to change the
running speeds preset in the parameters.
71
7
Acceleration time
8
Deceleration time
Used to set the acceleration and deceleration times.
72
9
Electronic thermal O/L relay
Used to set the current value of the electronic overcurrent protection
to protect the motor from overheat.
73
10
DC injection brake operation
frequency
11
DC injection brake operation time
12
DC injection brake voltage
13
Starting frequency
Used to adjust the stopping accuracy according to the load.
74, 75
14
Load pattern selection
Used to select the optimum output characteristic that matches the
application and load characteristics.
76
19
Base frequency voltage
Used to set the base voltage (e.g. motor's rated voltage).
70
52
DU/PU main display data selection
53
PU level display data selection
54
FM terminal function selection
Used to choose the monitoring and output signals.
88
55
Frequency monitoring reference
56
Current monitoring reference
Used to set the frequency and current values, which are referenced,
for the level meter.
90
57
Restart coasting time
58
Restart cushion time
Used to perform automatic restart operation after instantaneous
power failure or commercial power supply-inverter switchover.
91
3
Simple mode parameter