PARAMETERS
121
(6) Communication specifications for RS-485 communication
Operation Mode
Operation Location
Item
Communication
Operation from PU
Connector
External
Operation
Computer Link Operation
(inboard option used)
Run command (start)
Enable
Disable
Disable
Running frequency setting
Enable
Enable
(Combined
operation mode)
Disable
Monitoring
Enable
Enable
Enable
Parameter write
Enable (*4)
Disable (*4)
Disable (*4)
Parameter read
Enable
Enable
Enable
Inverter reset
Enable (*2)
Enable (*2)
Enable (*2)
Computer user program via
PU connector
Stop command (*3)
Enable
Enable
Enable
Run command
Disable
Disable
Enable (*1)
Running frequency setting
Disable
Disable
Enable (*1)
Monitoring
Enable
Enable
Enable
Parameter write
Disable (*4)
Disable (*4)
Enable (*4)
Parameter read
Enable
Enable
Enable
Inverter reset
Disable
Disable
Enable (*2)
Computer user program via
inboard option
Stop command (*3)
Disable
Disable
Enable
Inverter reset
Enable
Enable
Enable
Run command
Disable
Enable
Enable (*1)
Control circuit terminal
Running frequency setting
Disable
Enable
Enable (*1)
(*1) As set in the operation and speed command source parameters.
(*2) At occurrence of RS-485 communication fault, the inverter cannot be reset from the computer.
(*3) As set in Pr. 75.
(*4) As set in Pr. 77.
(7) Operation at alarm occurrence
Operation Mode
Fault Location
Status
Communication
Operation
(PU connector)
External
Operation
Computer link
Operation
(inboard option used)
Inverter operation
Stop
Stop
Stop
PU connector
Continued
Continued
Continued
Inverter fault
Communication
Inboard option
Continued
Continued
Continued
Inverter operation
Stop/continued (*5)
Continued
Continued
PU connector
Stop
Stop
Stop
Communication
error
(Communication
from PU connector)
Communication
Inboard option
Continued
Continued
Continued
Inverter operation
Continued
Continued
Stop/continued (*6)
PU connector
Continued
Continued
Continued
Communication
error
(Inboard option)
Communication
Inboard option
Stop
Stop
Stop
(*5) Can be selected using the corresponding parameter (factory-set to continue)
(*6) Can be selected using the corresponding parameter (factory-set to stop)
(8) Communication error
Fault Location
Error Message
Communication error
(Error in communication from PU
connector)
E.PUE
Communication error
(Computer link inboard option)
E.OP1 to E.OP3
4