PARAMETERS
102
4.2.32 Input filter time constant (Pr. 74)
Pr. 74 "filter time constant"
You can set the input section's internal filter constant for an external voltage or current frequency setting
signal.
#
Effective for eliminating noise in the frequency setting circuit.
#
Increase the filter time constant if steady operation cannot be performed due to noise. A larger setting
results in lower response. (The time constant can be set between approximately 1ms to 1s. with the setting
of 0 to 8. A larger setting results in a larger filter time constant.)
Parameter
Number
Factory
Setting
Setting Range
74
1
0 to 8
4.2.33 Reset selection/disconnection PU detection/PU stop selection
(Pr. 75)
Pr. 75 "reset selection/disconnection PU detection/PU stop selection"
You can select the reset input acceptance, PU (FR-DU04/FR-PU04) connector disconnection detection
function and PU stop function.
•
Reset selection
: You can select the reset function input timing.
•
PU disconnection detection
: When it is detected that the PU (FR-DU04/FR-PU04) is
disconnected from the inverter for more than 1 s, the inverter outputs
an alarm code (E.PUE) and comes to an alarm stop.
•
PU stop selection
: When an alarm occurs in any operation mode, you can stop the motor from
the PU by pressing the
STOP
RESET
key.
Parameter
Number
Factory
Setting
Setting Range
75
14
0 to 3, 14 to 17
<Setting>
Pr. 75
Setting
Reset Selection
PU Disconnection Detection
PU Stop Selection
0
Reset input normally enabled.
1
Reset input enabled only when the
protective function is activated.
If the PU is disconnected, operation
will be continued.
2
Reset input normally enabled.
3
Reset input enabled only when the
protective function is activated.
When the PU is disconnected, the
inverter output is shut off.
Pressing the
STOP
RESET
key
decelerates the motor to a stop only in
the PU operation mode.
14
Reset input normally enabled.
15
Reset input enabled only when the
protective function is activated.
If the PU is disconnected, operation
will be continued.
16
Reset input normally enabled.
17
Reset input enabled only when the
protective function is activated.
When the PU is disconnected, the
inverter output is shut off.
Pressing the
STOP
RESET
key
decelerates the motor to a stop in any
of the PU, external and
communication operation modes.