![Mitsubishi Electric FR-F500 Series Скачать руководство пользователя страница 150](http://html.mh-extra.com/html/mitsubishi-electric/fr-f500-series/fr-f500-series_instruction-manual_239240150.webp)
PARAMETERS
137
<Setting>
Refer to the following table and set the parameter as required:
Stall Prevention Operation Selection
$
$
$
$
...Activated
#
#
#
#
...Not activated
Pr. 156 Setting
Fast-Response
Current Limit
$
$
$
$
...Activated
#
#
#
#
...Not activated
Acceleration
Constant speed
Deceleration
OL Signal Output
$
$
$
$
...Operation continued
#
#
#
#
...Operation not
continued (Note 1)
0
$
$
$
$
$
1
#
$
$
$
$
2
$
#
$
$
$
3
#
#
$
$
$
4
$
$
#
$
$
5
#
$
#
$
$
6
$
#
#
$
$
7
#
#
#
$
$
8
$
$
$
#
$
9
#
$
$
#
$
10
$
#
$
#
$
11
#
#
$
#
$
12
$
$
#
#
$
13
#
$
#
#
$
14
$
#
#
#
$
15
#
#
#
#
$
16
$
$
$
$
#
17
#
$
$
$
#
18
$
#
$
$
#
19
#
#
$
$
#
20
$
$
#
$
#
21
#
$
#
$
#
22
$
#
#
$
#
23
#
#
#
$
#
24
$
$
$
#
#
25
#
$
$
#
#
26
$
#
$
#
#
27
#
#
$
#
#
28
$
$
#
#
#
29
#
$
#
#
#
30
$
#
#
#
#
31
#
#
#
#
#
Driving
$
$
$
$
$
100
Regenerative
#
#
#
#
$
Driving
#
$
$
$
$
101
(Note 4) Regenerative
#
#
#
#
$
Note 1: When "Operation not continued for OL signal output" is selected, the "E.OLT" alarm code
(stopped by stall prevention) is displayed and operation stopped.
(Alarm stop display "E.OLT")
2: If the load is heavy, the lift is predetermined, or the acceleration/deceleration time is short, the
stall prevention may be activated and the motor not stopped in the preset
acceleration/deceleration time. Therefore, set optimum values to the Pr. 156 stall prevention
operation level.
(When the output voltage reduces during stall prevention operation, an overcurrent trip will be less
liable to occur but the torque decreases. Set "0" in Pr. 154 when the torque may be reduced.)
3: In vertical lift applications, make setting so the fast-response current limit is not cativated. Torque
may not be produced, causing a gravity drop.
4: At the setting of "101", the fast-response current limit can be disabled in the driving mode as
compared to the setting of "100".