PARAMETERS
141
<Setting>
Refer to the following list and set the parameters:
Setting
Signal
Name
Functions
Relevant Parameters
Pr. 59 = 0
Low-speed operation command
Pr. 4 to Pr. 6
Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
0
RL
Pr. 59 = 1, 2*
Remote setting (setting clear)
Pr. 59
Pr. 59 = 0
Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to
Pr. 239
1
RM
Pr. 59 = 1, 2*
Remote setting (deceleration)
Pr. 59
Pr. 59 = 0
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
2
RH
Pr. 59 = 1, 2*
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 50
4
AU
Current input selection
Refer to page 10
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Automatic restart after instantaneous power failure selection
Pr. 57, Pr. 58, Pr. 162 to Pr. 165
7
OH
External thermal relay input**
The externally provided overheat protection thermal relay,
motor-embedded temperature relay, etc is operated to stop
the inverter.
Refer to page 166
10
X10
FR-HC, FR-CV connection (inverter operation enable)
Pr. 30
11
X11
FR-HC connection (instantaneous power failure detection)
(Only when FR-A5NR option is fitted)
Pr. 30
12
X12
PU operation external interlock
Pr. 79
13
X13
External DC injection brak start
Pr. 10 to Pr. 12
14
X14
PID control valid terminal
Pr. 128 to Pr. 134
16
X16
PU-external operation switch-over
Pr. 79
24
X24
PID forward-reverse action switching function
(NA, EC versions only)
Pr. 500 to Pr. 516
9999
No function
*: When Pr. 59 = "1" or "2", the functions of the RL, RM, RH and RT signals change as listed above.
**: Operated when the relay contact "opens".
Note: 1. One function can be assigned to two or more terminals. In this case, the terminal inputs are
OR’ed.
2. The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL) and
AU.
3. When the X10 signal (inverter operation enable signal for FR-HC, FR-CV connection) is not set,
the MRS terminal shares this function.
4. Use common terminals to assign the multi-speeds (7 speeds) and remote setting. They cannot
be set individually.
(Common terminals are used since these functions are designed for speed setting and need not
be set at the same time.)
5. When "7" is set in Pr. 79 and the PU operation external interlock (X12) signal is not assigned, the
MRS signal acts as this function.
4