PARAMETERS
113
<Computer programming>
(1) Communication protocol
Data communication between the computer and inverter is performed using the following procedure:
*1
*2
Computer
Inverter
↓
(Data flow)
Computer
↓
(Data flow)
Inverter
Data read
Data write
Time
1)
2)
3)
4)
5)
*1. If a data error is detected and a retry must be made, execute retry operation from the user program. The
inverter comes to an alarm stop if the number of consecutive retries exceeds the parameter setting.
*2. On receipt of a data error occurrence, the inverter returns “reply data 3)” to the computer again. The
inverter comes to an alarm stop if the number of consecutive data errors reaches or exceeds the
parameter setting.
(2) Communication operation presence/absence and data format types
Communication operation presence/absence and data format types are as follows:
No.
Operation
Run
Command
Running
Frequency
Parameter
Write
Inverter
Reset
Monitor-
ing
Para-
meter
Read
1)
Communication request is sent to the
inverter in accordance with the user
program.
A’
A
A
A
B
B
2)
Inverter data processing time
Present
Present
Present
Absent
Present
Present
No error*
(Request accepted)
C
C
C
Absent
E
E’
E
3)
Reply data from the
inverter
(Data 1) is checked for
error)
With error
(request rejected)
D
D
D
Absent
F
F
4)
Computer processing delay time
Absent
Absent
Absent
Absent
Absent
Absent
No error*
(No inverter
processing)
Absent
Absent
Absent
Absent
G
G
5)
Answer from computer
in response to reply
data 3)
(Data 3) is checked for
error)
With error
(Inverter outputs 3)
again.)
Absent
Absent
Absent
Absent
H
H
* In the communication request data given from the computer to the inverter, 10ms or more is also
required after "no data error (ACK)". (Refer to page 115)
(3) Data format
Hexadecimal data is used. Data is automatically transferred in ASCII between the computer and inverter.
•
Data format types
1) Communication request data from computer to inverter
*3
ENQ
*4
1
2
3
4
5
6
7
8
9
10
11
12
13
*3
ENQ
*4
1
2
3
4
5
6
7
8
9
10
11
*3
ENQ
*4
1
2
3
4
5
6
7
8
9
[Data write]
Format A
[Data read]
Format A'
Format B
Inverter
station
number
Instruction
code
*5
Waiting
time
Data
Sum
check
Inverter
station
number
Inverter
station
number
Instruction
code
Instruction
code
*5
Waiting
time
*5
Waiting
time
Data
Sum
check
Sum
check
←
Number of characters
←
Number of characters
←
Number of characters
4