PARAMETERS
155
<Output stop detection>
Td
STOP
START
Time
Time
Motor
Pr. 508: Output stop
cancel level
Pr. 507: Output stop
level
Pr. 506: Output stop
detection time
Output at stop
Output frequency
Process value
#
The output stops if the output frequency continues to be lower than the Pr. 507 value for longer than the
time set in Pr. 506.
When the setting is 9999, the output stop function is not performed.
Also, an output stop is not detected when the process value is not more than the Pr. 508 value or when the
start signal is off. It is not detected during auxiliary motor operation either.
Parameter Number
Name
Setting Range
Setting Increments
Factory Setting
506
Output stop detection time
0 to 3600s, 9999
0.1s
9999
#
You can set the set the output frequency value at which an output stop is detected. The output is stopped
when the output frequency continues to be lower than the Pr. 507 value for longer than the time set in
Pr. 506.
Parameter Number
Name
Setting Range
Setting Increments
Factory Setting
507
Output stop detection level
0 to 120Hz
0.01Hz
0Hz
#
You can set the process value at which a restart is made after the output stop. Set the ratio of the process
value to the set point.
Parameter Number
Name
Setting Range
Setting Increments
Factory Setting
508
Output stop cancel process value
level
0 to 100%
0.1%
100%
4