PARAMETERS
138
CAUTION
Always perform test operation.
Stall prevention operation performed during acceleration may increase the
acceleration time.
Stall prevention operation performed during constant speed may cause sudden speed
changes.
Stall prevention operation performed during deceleration may increase the
deceleration time, increasing the deceleration distance.
4.2.45 OL signal output timer (Pr. 157)
Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Number
Factory
Setting
Setting Range
Remarks
157
0
0 to 25 s, 9999
9999: No signal output
Set time (s)
Overload status (OL output)
OL output signal
<Setting>
Refer to the following table and set the parameter:
Pr. 157
Setting
Description
0
Output immediately.
0.1 to 25
Output after the set time (s) has elapsed.
9999
Overload alarm signal is not output.
Pr. 158
%
%
%
%
Refer to Pr. 54.
Pr. 190 to Pr. 195
(output terminal function selection)
Related parameters