Graphic Operation Terminal F930GOT
Additional Functions (in V.2.00 or later) 13
13-16
13.6.2
Observe status cycle
Set the cycle at which the F930GOT monitors whether the specified triggers are established.
Select "always" or "constant cycle".
-
Always:
Every time communication is performed between the F930GOT and the PLC, the
F930GOT monitors whether the specified triggers are established at every 200 to 300 ms.
-
Constant cycle: The cycle can be set to 1 to 60 seconds with the increment of 1 second.
At the set cycle, the F930GOT monitors whether the specified triggers are established.
13.6.3
Setting the triggers
Set the triggers to be monitored.
Up to two bit devices can be set.
-
Trigger 1: Set ON or OFF of a bit device.
-
Trigger 2: Set ON or OFF of a bit device.
•
When the trigger 1 and the trigger 2 are set, the F930GOT performs the operation
described in the next paragraph only when the both triggers are established.
•
Make sure to set the trigger 1. And set the trigger 2 if necessary.
Example: Trigger 1: "ON" is set.
Trigger 2: "OFF" is set.
Both triggers are established.
ON
OFF
ON
OFF
Содержание F930GOT-BWD-E
Страница 1: ...USER S MANUAL F930GOT BWD E ...
Страница 4: ...Graphic Operation Terminal F930GOT ii ...
Страница 6: ...Graphic Operation Terminal F930GOT iv ...
Страница 14: ...vi ...
Страница 60: ...Graphic Operation Terminal F930GOT Start up 2 2 10 MEMO ...
Страница 68: ...Graphic Operation Terminal F930GOT Screen Mode 3 3 8 MEMO ...
Страница 120: ...Graphic Operation Terminal F930GOT Creation of Display Screens 8 8 30 ...
Страница 200: ...Graphic Operation Terminal F930GOT Changeover of Display Screen FX PCS DU WIN E 10 10 18 ...
Страница 272: ...Graphic Operation Terminal F930GOT Additional Functions in V 2 00 or later 13 13 24 MEMO ...