-76-
(4)
Bypass - capacity control
The solenoid valves have bypass valves (SV1, SV4 and SV6) that allow bypassing of the high pressure and low
pressure sides and solenoid valves (SV22 and SV32) that control the capacity valve inside the compressor. Those
operation are as follows.
: Installed : Not Installed
SV1
SV4
SV6
SV22, SV32
Variable Capacity Unit
Constant Capacity Unit
Use
* The compressor of constant capacity unit starts in un-load operation in the initial start mode and during defrosting
only, and starts in full-load operation at all other times by SV22,23 switching.
Normally compressor capacity control is not performed.
1) Bypass Valve (SV6) (SV6 is open when ON, variable capacity unit only)
• The valve is set as follows according to whether the variable capacity unit No. 1 and No. 2 compressors are
operating.
No. 1 Compressor No. 2 Compressor
SV6
Stopped
Stopped
OFF
Operating
Stopped
ON
Operating
Operating
OFF
Maintenance of high-pressure/low-pressure,
discharge temperature
Controls the
compressors’
internal volume
control valve
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......