-116-
1
2
3
4
5
During cooling operations, required refrigerant amount tends to increase (refrigerant in accumulator decreases)
in proportion to increase in the number of operating indoor units. However, the change of increase rate is small.
During heating operations, liquid level of accumulator is the highest when all the indoor units are operating.
Discharge temperature hardly changes when increasing or decreasing refrigerant amount with accumulator
filled with refrigerant.
Compressor shell temperature is 20 ~ 70 degrees higher than low pressure saturation temperature (TH2) when
refrigerant amount is appropriate.
→
Judged as over replenishment when temperature difference from low pressure saturation temperature (TH2)
is 10 degrees or less.
Tendency of
discharge
temperature
During cooling operations, at high ambient temperature the
discharge temperature tends to rise.
During heating operations, at low ambient temperature the
discharge temperature tends to rise.
The lower the operating frequency is, the higher the discharge temperature
tends to become because of deteriorated compressor efficiency.
Comparison including
control system
§
REFRIGERANT AMOUNT ADJUSTMENT
[1] Operating Characteristics and Refrigerant Amount
The followings are operating characteristics and refrigerant amount which draw special attention.
[2] Adjustment and Judgement of Refrigerant Amount
(1)
Symptom
The symptoms shown in the table below are the signs of excess or lack of refrigerant amount. Be sure to adjust the
amount of refrigerant in refrigerant amount adjustment mode, by checking operation status, judging refrigerant amount,
and performing LED monitor display with LED Dip S/W1, 1-10, for overall judgement of excess or lack of refrigerant
amount.
1
2
3
4
Error stop at 1500 remote controller display
(excessive refrigerant replenishment)
Operating frequency does not fully increase, thus resulting in
insufficient capacity
Error stop at 1102 remote controller display
(discharge temperature trouble)
Error stop at 1501 remote controller display
(low refrigerant trouble)
Excessive refrigerant replenishment
Insufficient refrigerant replenishment
By clarifying the relationship between the refrigerant amount and operating characterstics, conduct service activities such
as decision on the amount and adjustment of refrigerant on the market.
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......