-163-
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
5201
5301
Pressure
sensor
abnormality
(Variable
capacity unit)
IAC sensor/
circuit
abnormality
(Variable
capacity unit)
When pressue sensor detects
or less during
stops with 3 minutes restarting
mode, and restarts if the detected
pressure of pressure sensor ex-
ceeds
If the detected pressure of sen-
sor is less than
immediately before restarting,
error stop is commenced
displaying 5201.
Under 3 minutes restar ting
mode, LED displays intermittent
fault check.
During 3 minutes after com-
pressor start, defrosting and 3
minutes after defrosting opera-
tions, trouble detection is ig-
nored.
If IAC 3 Amps is detected just
before the inverter starts, or
If IAC 3 Amps is detected dur-
ing inverter operation after 5
seconds has passed since the
inverter started when the INV
board’s SW1-1 is OFF.
[Inverter error detail : 6]
If the current sensor (ACCT)
miss-wiring is detected during
inverter operation.
[Inverter error detail : 13]
1)
2) Inner pressure drop due to a leak-
age.
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire.
6) Faulty thermistor input circuit of
MAIN board.
1) Contact is faulty.
2) The current sensor (ACCT) is con-
nected with wrong polarity.
3) The wiring is defective
4) The Ac current sensor (ACCT) is
defective.
5) The IPM is defective.
See
Troubleshooting of pressure
sensor
.
Check the contacts of CNACCT on the
INV board.
Check the ACCT_U, W polarity
with below drawing.
Check 1. connections.
2. contact at the connectors.
3. for broken wires in the follow-
ing wiring.
CNDR2-CNDR1
CN15V2-CN15V1
IPM-MC1
To judgefailure of ACCT, go to “individual
Parts Failure Judgment Methods.”
Check the IPM.
Judge that the IPM is fauly, (Go to “In-
dividual Parts Failure Judgment Meth-
ods.”)
ACCT_U
U
ACCT_W
IPM-output
phase U
IPM-output
phase W
Compressor-input
phase U
Compressor-input
phase W
Red wire
Black wire
W
0.098MPa imediately
before restarting.
0.098MPa
operation, outdoor unit once
0.098MPa
Pressure sensor trouble.
1
2
3
4
1
2
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......